IOT USA
M200T Analog Output Module
M200T - 2 Analog Output Ethernet Remote Module (2AO 12bit)
The M200 Ethernet Remote I/O module provides 2 analog outputs, 12-bit resolution, and supports 0~10VDC signal output. All the I/O with high sampling frequency and special filtering strategy to ensure its reliability.
Introduction
The M200 Ethernet Remote I/O Module is an industrial class, isolated designed, high reliability, high stability and high precision data acquisition module. It features an embedded 32-Bit High Performance Microprocessor MCU and an Integrated 1 Industrial 10/100M adaptive Ethernet module inside. It provides multiple I/O, supports standard Modbus TCP, can be intergraded into a SCADA, OPC server, and other automation systems. It is designed for working in harsh industrial environments and is widely used in a variety of industrial automation, security monitoring systems, automatically measurement and control systems.
The M200T provides an RS485 interface, through the RS485 bus and it can cascade Modbus RTU I/O devices or Modbus RTU meters, e.g.: a variety of digital input or digital outputs, analog inputs or outputs, thermal resistance IO module combination, save costs. At the same time, the Ethernet Remote I/O module has a register mapping function, the cascade Modbus RTU I/O data are automatically collected to the mapping memory area, the Modbus TCP Client query without waiting then can get a quick response to meet industrial time requirements.
The M200T Ethernet Remote I/O module provides 2 analog outputs, 12-bit resolution, and supports 0~10VDC signal output. All of the I/O’s feature high sampling frequency and special filtering strategy to ensure its reliability.
Features
1. Embedded 32-Bit High Performance Microprocessor MCU, built-in watchdog.
2. Wide range power supply 24 ~ 36VDC with over voltage and phase-reversal protection.
3. Management and configuration via LAN connection configuration software for effortless operation and maintenance.
4. Integrated 10/100M adaptive Ethernet module, supports Modbus TCP protocol.
5. 2 analog output, 12-bit resolution, supports 0-10VDC.
6. High sampling frequency and special filtering strategy to ensure reliability.
7. 1 RS485 Serial port, supports Modbus RTU/ASCII Master, can extend I/O modules.
8. Supports register mapping function and extends I/O inquiry strategy.
9. Supplies 1 channel 24~36VDC power source output for external devices, saving wiring cost.
10. LED (Light Emitting Diode) instructions work status, with reset button to reset, easy on-site installation and commissioning.
11. Using metal shell, protection class IP30. Metal shell and system security isolation, especially suitable for industrial applications in the field.
Specifications
Analog Output
Type |
Differntial Input |
Resolution |
12 bits |
Output Range |
0 to 10 VDC |
Drive Current |
1A (max) |
Accuracy |
±0.1% FSR @ 25ºC ±0.3% FSR @ -10 and 60ºC ±0.5% FSR @ -40 and 75ºC |
Load Resistor |
Internal Register, 400 ohms |
Isolation |
No |
Working Power Requirements
Input Voltage |
24 to 36 VDC, Peak Voltage; +40VDC Power Consumption: Less Than 3W |
Input Current | 139mA @24VDC |
Power Output
Output Voltage |
12 to 36 VDC |
Output Current | 139mA @ 24 VDC |
LAN
Ethernet | 10/100Mbps RJ45 ports |
Protection | 15KV ESD Protection |
Protocols | Modbus TCP, TCP/IP |
Max TCP Connection | 5 |
Serial Port
RS485 | MODBUS- RTU Protocol, Modbus-ASCII Protocol |
Protection | 15KV ESD Protection |
Modbus Slave Address | 1-255 |
Baud Rate | 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200, 128000Bps |
Mapping Registers | Bit Type: 300 Registers, 16-Bit Type: 300 Registers |
Physical Characteristics
Wiring | I/O Cable Max. 14AWG |
Dimensions | 105mm x 88mm x 30mm |
Weight | Under 205grams |
Mounting | DIN Rail or Wall |
Environmental Limits
Operating Temperature |
Standard Model: -10 to 60°C (14 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Altitude | Up to 3000m |
Downloads
M200T - Data Sheet Download
M200T User Manual
Applications
Typical applications:
- BTS Monitoring.
- Security Alarm System applications.
- Supervision and monitoring alarm systems.
- Automatic monitoring system.
- Vending Machines security protection.
- Pumping Stations, Tanks, Oil or Water levels.
- Buildings and Real Estate.
- Weather Stations.
- River Monitoring and Flood Control.
- Oil and gas pipelines.
- Corrosion protection.
- Temperatures, water leakage applications.
- Wellheads, boat, vehicle.
- Energy saving, streetlights control system.
- Valve controls.
- Transformer stations
- Unmanned machine rooms.
- Control room application.
- Automation System, M2M.
- Access Control System.
- 21. PLC Gateway, PLC Remote Monitoring.